John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 21

Advertising
background image

21

TABLE 5

MANIFOLD GAS PRESSURE IN INCHES

OF WATER COLUMN (ALL MODELS*)

TYPE OF GAS

NATURAL

PROPANE

3.5

10.0

Gas pressure specified in Table 5, refer to flow pressure taken at

pressure tap of automatic gas valve while heater is operating.

TABLE 6

APPROXIMATE TIME REQUIRED TO CONSUME

1 CU. FT. OF GAS AT FULL CAPACITY

INPUT

RATE

(BTUH)

TYPE

OF

GAS

BTUH

PER

CU. FT.

TIME REQ’D

TO CONSUME

1 CU. FT.

OF GAS

120,000

NATURAL

PROPANE

1050

2500

31. 5 SEC.

75.0 SEC.

154,000

NATURAL

PROPANE

1050

2500

24. 5 SEC.

58.4 SEC.

199,000

NATURAL

PROPANE

1050

2500

19.0 SEC.

47.4 SEC.

251,000

NATURAL

PROPANE

1050

2500

15.06 SEC.

35.1 SEC.

275,000

NATURAL

PROPANE

1050

2500

13.75 SEC.

32.2 SEC.

305,000

NATURAL

PROPANE

1050

2500

12.4 SEC.

29.5 SEC.

365,000

NATURAL

PROPANE

1050

2500

10.4 SEC.

24.7 SEC.

390,000

NATURAL

PROPANE

1050

2500

9.5 SEC.

22.6 SEC.

Figures shown are valid for 0-2000 ft.(0-610m) installations. See

“HIGH ALTITUDE INSTALLATIONS” for deration requirements

over 2000 ft.(610m).

TABLE 7

PILOT BURNER INFORMATION

TYPE OF

PILOT BURNER

RATED

MODEL

GAS

PART NUMBER

ORIFICE

(WITH ORIFICE)

SIZE

ALL

NATURAL

9004541215

0.018

MODELS

PROPANE

9004542215

0.014

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

Advertising
This manual is related to the following products: