John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 16

Advertising
background image

16

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE

TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE

CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT

TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE

BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT

WATER SUPPLIED TO FIXTURES.

TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE

WITH RECIRCULATION OF SANITIZING LOOP

NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER

CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING

MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING

THE RINSE OPERATION AND OPEN (OFF) WHEN DISHWASHER

IS NOT OPERATING OR WHEN ON LONG STANDBY.

NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN

UNINSULATED TEE BEYOND THE DISHWASHING MACHINE

TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD BE

SET AT 185°F (85°C).

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE

DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE

TANK.

* TEMPERED WATER LOOP, IF USED, CONNECT TO

POINT “A”.

**PIPE RELIEF VALVE TO OPEN DRAIN.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW

PREVENTER, CHECK VALVE OR WATER METER WITH

CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF

WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.

INSERT A

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

Advertising
This manual is related to the following products: