Technical data venting, table 3 (continued) – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 11

Advertising
background image

11

TECHNICAL DATA VENTING, TABLE 3 (Continued)

MODEL (A)JWSM65251

Input: 251,000 Btuh Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (inches)

251,000

1 Ft.

-

-

-

-

-

-

8

8

251,000

-

-

-

8

8

8

8

8

251,000

3 Ft.

-

8

8

8

-

8

7

7

Number

of Heaters

Combined Input in

Thousands of Btuh

Manifold and Common Vent Diameter (In inches)

2

3

4

502

14

12

12

10

10

10

8

8

753

14

14

14

12

12

12

10

10

1004

18

16

16

14

14

14

12

12

MODEL (A)JWSM100275

Input: 275,000 Btuh Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

275,000

2 Ft.

-

-

-

-

-

8

8

8

275,000

3 Ft.

-

-

-

8

8

8

8

8

Number

of Heaters

Combined Input in

Thousands of Btuh

Manifold & Common Vent Diameter

2

550

-

-

-

12

10

10

10

10

3

825

-

-

-

14

14

12

12

12

4

1100

-

-

-

16

14

14

12

12

MODEL (A)JWSM65305

Input: 305,000 Btuh Total Vent Height (Feet)

Draft Hood: 8”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (inches)

315,000

1 Ft.

-

-

10

10

10

10

10

10

305,000

2 Ft.

10

10

10

10

10

10

8

8

365,000

3 Ft.

10

10

10

10

10

8

8

8

Number

of Heaters

Combined Input in

Thousands of Btuh

Manifold and Common Vent Diameter (In inches)

2

3

4

610

14

14

12

12

12

10

10

8

915

16

16

16

14

14

12

12

12

1220

18

18

16

16

16

14

14

12

MODEL (A)JWSM65365, (A)JWSM100390

Input: 365,000, 399,000 Btuh Total Vent Height (Feet)

Draft Hood: 8”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

365,000

1 Ft.

-

-

-

-

-

10

10

10

400,000

-

-

-

-

-

-

10

10

365,000

2 Ft.

12

12

10

10

10

10

10

10

400,000

12

12

12

12

10

10

10

10

365,000

3 Ft.

10

10

10

10

10

10

10

10

400,000

12

10

10

10

10

10

10

10

Number

of Heaters

Combined Input in

Thousands of Btuh

Manifold & Common Vent Diameter (inches)

2

730

14

14

14

12

12

12

10

10

800

16

14

14

14

12

12

10

10

3

1095

18

18

16

16

14

14

12

12

1200

18

18

18

16

16

14

14

12

4

1460

20

20

18

18

16

16

14

12

1600

22

20

20

18

18

16

14

14

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)