ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE

STORAGE WITH OR WITHOUT RECIRCULATION

HEATER WITH OR WITHOUT MIXING VALVE

HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP

NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C)

WATER CIRCULATION. INSTALL ON OR

CLOSE TO DISHWASHING MACHINE. TOGGLE

SWITCH MUST BE CLOSED (ON) DURING THE

RINSE OPERATION AND OPEN (OFF) WHEN

DISHWASHER IS NOT OPERATING OR WHEN

ON LONG STANDBY.

NOTE 2: INSTALL LINE TEMPERATURE CONTROL

IN AN UNINSULATED TEE BEYOND THE

DISHWASHING MACHINE TAKEOFF

IN THE SANITIZING LOOP. CONTROL

SHOULD BE SET AT 185°F (85°C).

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING

LOOP FLOW RATE DOES NOT CAUSE

UNNECESSARY TURBULENCE IN THE

TANK.

* PIPE RELIEF VALVE TO OPEN DRAIN.

INSTALL IN ACCORDANCE WITH LOCAL

CODES.

CIRCULATING RETURN LINE CONNECTIONS.

- T E M P E R E D WAT E R L O O P, I F U S E D ,

CONNECT TO POINT “R”.

- STORED TEMPERATURE WATER LOOP, IF USED,

CONNECT TO COLD WATER INLET.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW

PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,

PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER

SYSTEM MUST BE PROVIDED.

DANGER

TEMPERATURE SETTING SHOULD NOT

EXCEED SAFE USE TEMPERATURE AT

FIXTURES. SEE WATER TEMPERATURE

CONTROL WARNING ON PAGE 25. IF HIGHER

PREHEAT TEMPERATURES ARE NECESSARY

TO OBTAIN ADEQUATE BOOSTER OUTPUT,

ADD AN ANTI-SCALD VALVE FOR HOT WATER

SUPPLIED TO FIXTURES.

INSERT A