Figure 34 — User Input Configuration: Setting the Trigger Type

Figure 35 — User Input Configuration: Setting the Logic Level

3. Select Edge Trigger.

4. Select Low from the Level drop down menu. The User Input goes to logic level "low" whenever it is triggered.

5. Select User Alarm On from the Action #1 drop down menu.

Procedure

1. Select UPS Maintenance > User Input to display the User Input Configuration window.

2. In the Input 1 column, select the Type down arrow to display the 3 types of available triggers: Edge Trigger,

Level Toggle, and Level Alternative. For more information on how triggers work, see "Appendix B - Types of

Triggers" on page 88.

UPS Maintenance > User Input

Three programmable User Inputs exist. Their functions are similar to the Dry Contact relays. Supported functions

include: (a) Shutdown, (b) User Alarm, (c) Self Test, and (d)Inverter Off.

Any user input can be configured to perform a certain action in response to different trigger types and logic

levels. For example, if you want the Alpha FXM to issue an intrusion alarm when the door is opened, you need to

wire the door with a switch that triggers a user input every time the door is opened.
The following procedure describes how User Input 1 can be configured as an intrusion alarm input.