017-230-B4 Rev B

NOTE:

The Battery Runtime Remaining algorithm attempts to calculate the health of the battery to get a more accurate

prediction of the remaining battery runtime. An accurate estimate of the battery health requires that at least one

battery discharge greater than 20% depth of discharge has taken place since the unit was switched on. When

the unit is powered up from an off state, the algorithm assumes that a new battery is connected to the unit. Each

discharge of greater than 20% will result in a new calculation for the relative battery health. This value is then

used in the Battery Runtime Prediction algorithm to compensate for an aging battery. We recommend that the

user set up a periodic (every 6 months) battery test with a depth of discharge of at least 20%.
The Battery Runtime Remaining algorithm relies heavily on the battery voltage to predict the remaining runtime.

This results in a less accurate predicted runtime during periods when the battery voltage is changing rapidly. The

battery voltage typically changes rapidly during the first few minutes of discharge when the unit switches from

charging to discharging while the unit is in the Inverter mode. The battery voltage may also change rapidly during

the last 20% of the discharge time when the battery is almost drained.

In the Battery Configuration table, Temperature Compensation (default 0.0mV/Cell/°C for bulk charger) and

Max Charger Current

have the same function as the Standard charging method.

The following three parameters are only available when the Bulk battery charging method is selected:

Parameter

48V

24V

Default

Minimum

Maximum

Default

Minimum

Maximum

Max Charger Voltage (Vdc)

53.5

52

56

26.8

26

28

Float Charger Voltage (Vdc)

53.5

52

56

26.8

26

28

Low Voltage Warning*(Vdc)

44

44

47

22

22

23

*Low voltage warning value has to be higher than Low Voltage Disconnect and lower than Low Voltage

Reconnect

Low Voltage Disconnect

and Low Voltage Reconnect have the same function as the Standard charging

method.

Bulk Charging Method
The Battery maintenance page has two tables: Battery Primary Configuration and Battery Configuration.
In the Battery Primary Configuration table, select Bulk battery charging method.

Figure 23 — UPS Maintenance: Battery, Bulk charging method