Troubleshooting, 1 procedure, Table p a – Alpha Technologies FXM 650, 1100, 2000 UPS User Manual

Page 80

Advertising
background image

017-230-B4 Rev B

78

8. Troubleshooting

When the front panel alarm LED is illuminated or flashing, the Alpha FXM has a malfunction. The alarm and fault

submenus describe the malfunction. The Alpha UPS Monitor can also be used for troubleshooting.

8.1 Procedure

1. Press the SELECT button.

2. The LCD may display one or more conditions in the following table.

3. Press the SCROLL button to see if more than one malfunction is present.

4. To clear the malfunction from the screen, press and hold the SELECT button for 5 seconds.

Table P — Alarm Submenu

LCD Shows

Problem Description

What To Do

Over Load

The Alpha FXM is overloaded.

Remove excess loads.

Batt Temp High

The battery temperature is above the

specification limit.

If used, ensure that the battery fan

is working. Contact Alpha Technical

Support to purchase an upgrade if

required.

Batt Temp Low

The battery temperature is below the

specification limit.

Use optional battery heating mats or

heater. Contact Alpha technical support

to place the order.

Batt Low Warning

The batteries are almost discharged. Also see

Low Battery Warning in "UPS Maintenance >

Battery" on page 38.

Ensure that the Alpha FXM charger is

working. If the charging voltage is low,

the battery may need to be replaced.

FAN Alarm

The fan has failed.

Contact Alpha technical support. The

fan is not a replaceable part.

Temp Probe Unplug

The temperature probe is unplugged.

Plug it back into the Alpha FXM or

change the probe.

User Input Alarm

When the user input is shorted. See "UPS

Maintenance > User Input" on page 46

Check the user input parameters.

In Freq Out Of Range

The line frequency is outside of the Alpha FXM

allowable range. The Alpha FXM goes into

Inverter mode.

Info only.

Weak Battery

The battery is being monitored continuously

in the background in Line mode. This alarm

is issued if the battery did not pass the

background scan.

Check the battery life and replace the

battery if necessary.

Battery Test

The Alpha FXM is performing a battery test.

Info only.

Batt Breaker Open

The battery breaker is opened.

Ensure the battery breaker is

functioning.

DC_Overload

Batteries lose their ability to store power as

they age. When a battery string is charging,

the status of the battery voltage is checked

every three minutes. An alarm is generated if

the battery voltage continues to drop while the

batteries are charging.

Info only.

Keep Alive Failure

The Alpha FXM failed to restore

communication by resetting power using keep

alive feature

Turn off keep alive feature to clear the

alarm.

AC Breaker Open

The AC breaker is open.

Ensure the AC breaker is functioning.