5 hyperterminal interface – Alpha Technologies FXM 650, 1100, 2000 UPS User Manual

Page 62

Advertising
background image

017-230-B4 Rev B

60

6.5 HyperTerminal Interface

The Alpha FXM front panel has a DE-9 female connector. When connected to a PC with Windows HyperTerminal

or other terminal emulation software, the Alpha FXM can be remotely monitored and controlled with its command-

line system.
The following subsections describe the operation of the Alpha FXM via the RS232 interface and Windows

HyperTerminal:
• Using the Main menu
• Adjusting and controlling the Alpha FXM
• Programming the dry contacts and the clock
• Viewing the 200-event log

6.5.1 Set-up

1. Connect a 9-pin, fully shielded, straight-through DE-9 to DE-9 connector cable between the computer port

and the Alpha FXM port.

2. Use Device Manager to locate which COM port is connected to the UPS.

3. Open HyperTerminal (Start>All Programs>Accessories>Communications>HyperTerminal).

4. Enter a name for the connection (e.g. FXM) and click OK.

5. Under Connect Using choose the COM port found in step 2 and click OK.

6. Set the following parameters and click OK:
Bits per second: 2400
Data bits: 8
Parity: None
Stop bits 1
Flow control: None.

7. Click on the Properties icon (far right on the toolbar). Go to Settings>ASCII Setup. Check Echo typed

characters locally

. Click OK.

8. Press Enter and the FXM main menu should appear.