Troubleshooting est controllers (pwm) - continued – Anemostat EST User Manual

Page 32

Advertising
background image

32

Troubleshooting EST Controllers (PWM) - continued

EVO/ECM Series

Control Test Procedure

Variable Speed Test

The motor should be running to perform this test.

Set the multimeter to read 24Vdc.

1. Touch the black lead to the common (Green) wire on

the 4 pin motor connector.

2. Touch the red lead to the Speed (Red) wire on the 4

pin motor connector.

3. Set the EVO/ECM series controller to full speed.

4. The Dc voltage should be equal to the voltage on the white wire (~22Vdc). The motor

should run at full speed.

5. If the motor does not run at full speed, the cable may be defective.

6. Go to the control connector on the motor.

7. Insert the black meter lead into the connector shell hole

containing the single green wire.

8. Insert the red meter lead into the connector shell hole

containing the Red wire. The DC voltage should equal to the
voltage on the white wire (~22Vdc). If it is not, the control cable
is defective. If the voltage is ~22Vdc and the motor does not
run at full speed, contact the equipment manufacturer for further
instructions.

Advertising
This manual is related to the following products:

QST, QPT