Model est number description – Anemostat EST User Manual

Page 4

Advertising
background image

4

Model EST Number Description

Digit 1, 2, 3 - Model

EST

Series flow fan powered terminal with ECM motor

Digit 4 - Heat options

S

Standard

W

Hot water coil

E

Electric heat

Digit 5, 6, 7, 8 - Fan Horsepower and Primary inlet size

3306 1/3 hp 6” inlet
3307 1/3 hp 7” inlet
3308 1/3 hp 8” inlet
3309 1/3 hp 9” inlet
3310 1/3 hp 10” inlet

5006 1/2 hp 6” inlet
5007 1/2 hp 7” inlet
5008 1/2 hp 8” inlet
5009 1/2 hp 9” inlet
5010 1/2 hp 10” inlet
5012 1/2 hp 12” inlet
5014 1/2 hp 14” inlet

Digit 9 - Casing Construction

B

single wall 20ga. Steel (standard)

E

double wall 22ga. Steel
(1/2” glass fiber insulation)

F

low temp casing
(1” matte faced glass fiber insulation)

Digit 10 - Insulation and Treatment

0 None
1

1/2” matte-faced glass fiber insulation
(double wall only)

2

1” matte-faced glass fiber insulation (standard)
(also req’d for low temp casing)

3

1/2” foil-faced glass fiber
(tape over all insulation edges)

4

1” foil-faced glass fiber
(tape covers insulation edges)

5

3/8” closed cell insulation (fiber free)

Digit 11 - Control Type

0 None
P

Pneumatic

A

Electronic Analog

F

Supplied by others – factory mounted

Digits 12, 13, 14, 15 - Control Package

0000 None (field supplied by others)
XXXX Refer to available control packages

Digit 16 - Control location
(determined by facing inlet)

L

left hand

Digits 17, 18, 19, 20 - Primary air minimum airflow

0000

None specified

XXXX Specify minimum airflow setting in CFM

Digits 21, 22, 23, 24 - Primary air maximum airflow

0000

None specified

XXXX Specify maximum primary airflow setting in CFM.

Digits 25, 26, 27, 28 - Fan CFM

0000

None specified

XXXX Specify fan CFM.

Digit 29 - Heating coil and connection location (determine
by facing inlet)

0 None
A

One-row hot water coil - right hand

B

One-row hot water coil - left hand

C

Two-row hot water coil - right hand

D

Two-row hot water coil - left hand

K

Electric heat - connections same side as digit 16

Digit 30 - Fan Motor Voltage

1

115V/ 1 Ph./ 60 Hz.

2

277V/ 1 Ph./ 60 Hz.

3

240V/ 1 Ph./ 60 Hz.

Digit 31 - Electric Coil Voltage and Steps

0 None
A

208V/ 1 Ph/ 60Hz. 1 step

B

208V/ 1 Ph/ 60Hz. 2 step

C

208V/ 1 Ph/ 60Hz. 3 step

D

240V/ 1 Ph/ 60Hz. 1 step

E

240V/ 1 Ph/ 60Hz. 2 step

F

240V/ 1 Ph/ 60Hz. 3 step

G

277V/ 1 Ph/ 60Hz. 1 step

H

277V/ 1 Ph/ 60Hz. 2 step

J

277V/ 1 Ph/ 60Hz. 3 step

K

208V/ 3 Ph/ 60Hz. 1 step

L

208V/ 3 Ph/ 60Hz. 2 step

M

208V/ 3 Ph/ 60Hz 3 step

N

480V/ 3 Ph/ 60Hz. 1 step

P

480V/ 3 Ph/ 60Hz. 2 step

R

480V/ 3 Ph/ 60Hz. 3 step

Note: 3 steps not available with night setback control packages
Digits 32, 33. 34 - Electric coil KW

000 None
XXX Refer to notes for allowable range

Digit 35 and over - Options and Accessories

C1

Unit mounting brackets

C2

Manual damper locking quadrant (shipped loose)

C4

Hinged front panel control enclosure

C5

Discharge collar (“S” units only)

D3

Line voltage SPST disconnect switch (120V, 277V)

D5

Line voltage power-fusing
(fuse and block for 120V, 277V)
(terminal selector block standard)

D8

Fan Relay, 24 VAC Coil, SPST / N.O.
(for DDC controls by others)

D9

24 VAC Electric Actuator

DA

24 VAC Transformer, 40 VA

E1

Non-fused interlocking disconnect switch
for Electric heat

E2

Electric heat Mercury de-energizing contactors

E3

Electric heat power fusing
(fuses and fuse blocks)

E4

Electric heat manual reset secondary thermal cutout

E6

AirFlow proving switch

F1

One inch throwaway filters

K1

0-10 VDC input signal from DDC controller

K2

Manual fan adjust via screwdriver w/on-off position

K3

4-20 mA input signal from DDC controller

K4

Manual fan adjust via 2 rotary switches

K5

Manual selection 1 of 4 pre-programmed fan flow rates

K6

Factory set fan CFM

Standard Digits

1-3

4

5,6

7,8

9

10

11

12-15

16

17-20

21-24

25-28

29

30

31

32-34

35-36

37-38

39-+

Description

Model

Heat

HP

Inlet

Casing

Insul

Cntrl

Cntrl

LH

Min

Max

Fan

Heat

Fan

Coil

Elec

Opt

Opt

Opt

Num

Type

Pkg

CFM

CFM

CFM

Config

VAC

VAC

KW

Example

EST

E

10

14

B

1

A

5001

L

900

2000

2000

K

2

N

08.0

E1

F1

K2

7507

3/4 hp 7” inlet

7508

3/4 hp 8” inlet

7509

3/4 hp 9” inlet

7510

3/4 hp 10” inlet

7512

3/4 hp 12” inlet

7514

3/4 hp 14” inlet

1009 1 hp 9” inlet
1010 1 hp 10” inlet
1012 1 hp 12” inlet
1014 1 hp 14” inlet
1016 1 hp 16” inlet

Must be 4 wire
WYE configuration

Advertising
This manual is related to the following products:

QST, QPT