PRODUCT FEATURES

CONSTRUCTION

The chiller is built on a tubular steel base frame; with a 16 gauge powder coated steel

cabinet. Components are internally mounted on a 16 gauge galvanized steel base. All

of the access panels can be removed without tools. The electrical components are

enclosed in a 2 compartment weather proof enclosure.

REFRIGERATION SYSTEM

The chiller equipped with two 7.5 ton, nominally capacity, compressor/evaporator

modules. Each module has one hermetically sealed scroll compressor, one brazed plate

evaporator (316 SS plates), TEV, filter drier, sight glass and liquid/suction heat

exchanger and safety switches. The compressor has suction and discharge isolation

valves for ease of compressor replacement. Each system has a receiver with isolation

valves to allow the entire refrigerant charge to be pumped into the receiver when

removal of the module if needed. Each module is connected to an independent

condenser circuit. The condenser utilizes two 1-HP 1725 RPM motor with 24-inch

propeller to reject heat. The motor speed is controlled by a variable speed drive (FSD

or VFD) for controlling head pressure.

THE REFRIGERATION SYSTEM USES R-22

Each refrigeration system module is independent. One can be removed from the system

while the other is operating. Caution must be taken as high voltage electricity can

create personal injury and lead to death.

CHILLED WATER SYSTEM

The chiller installed with two identical pumps; they are redundancy pumps. A paddle

type flow switch, mounted on the return line of the chilled water loop, controls the

operation of these pumps. In addition, the pump will rotate it operation on a daily

basis. The default change over time is 23 o’clock. This time can be changed to

customer desire. A single set of chilled water connection is provided at the front of the

chiller

Inside the chiller is a 70-gallon, double wall insulated reservoir. The inner layer is 304

stainless steel and the outer layer is powder coated steel. There is 1” of foam in

between the layers. A 1” overflow (vent), sight glass, and 1” fill fitting is installed on the

main access side of the chiller. There is also a 1 2” drain. Since the reservoir is vented

to atmosphere, a backflow kit is provided to prevent water from flowing out of

Advertising