TROUBLE SHOOTING


ALARM CONDITIONS

POSSIBLE CAUSES

CHECKS & REPAIR

Low Pressure Circ. #1 or
#2

Low in Gas due to leak

Liquid line sol. Valve not
energizing.

Inadequate return water.


Ambient Temperature

*Check for leak & Repair

*Verify valve is good by
applying 24 vac directly.

*Check and clean
strainer.

*If ambient temp below
20

°F additional gas is

needed.

High Pressure Circ. #1 or
#2

Bad Fan Motors

Restricted flow through
condenser.



Failure VFD



Over Charging


Bad Compressor

*Manually turn on fan
and check current.

*Condenser clogged due
to surrounding debris, use
water spray.

*Check alarm status &
refer to VFD manual for
instructions.

*Make sure sufficient
charge to system.

*This only noticeable after
compressor moves 10
times, a big rattling noise
appears.

High Pressure Sensor
Failure # 1 and #2

Bad Pressure Transducers Replace the device with

same spec.

Float

Water Solution low in the
reservoir

*Add Solution