TANK FILL

Use the 1” Top Fill located on top of the unit to fill the chiller.

DEIONIZED WATER

The quality of the water used in this chiller will determine its useful life, and can void its warranty.
Schreiber chillers are suitable for use with De Ionized water with a resistance between 2,000 to
166,000 Ohms. Higher resistance will require the water circuit to be free of all Copper and
Copper alloys. Contact Schreiber for specific details. Water resistance below 2,000 Ohms will
require some form of water treatment such as; De Ionization, reverse osmosis, or softening.
Failure to ensure proper water quality will result in corrosion and premature failure of the chiller,
and will void the chiller warranty.

TESTING STANDARDS

Schreiber Engineering Chillers are certified by ETL value under UL’s 1995 standard 2

nd

ED. The system is

tested under 250 pounds of pressure. All motors have internal overload protection except where noted.

ELECTRIC – POWER

A good test to make sure power is off to the unit is to turn on the water pump switch. If power is on, the light
on this pump will be on. We recommend you take caution in all judgments about the power being on. The
best test to find if the power is on is to use a voltmeter. Please Note: A single – phase condition can cause
a pilot light to be out and still have voltage to the unit.

CONT. WATER CHILLER STARTING CHECKLIST