to allow for flow disruptions caused by a changed in valve position or bubbles in the

system.

Backflow Kit

Since the chilled water reservoir is vented to the atmosphere, water in pipes above the

water level of the reservoir will flow back and overflow the reservoir when the pumps
are shut off. To prevent this, a backflow kit consisting of a solenoid valve on the return

line on chilled water return, and a check valve on the pump discharge is provided. The

solenoid valve is a normally closed valve that is energizes whenever the pump contactor
is energized.

The backflow kit also keeps the entire piping loop full of water during shut down. In
some cases (including startup) the pump will start when the pipe is not full. Since the

flow switch is on the return line, the pump may alarm on a flow error on pumped

startup, because the time required to fill the pipes and trigger the flow switch was
longer than the time delay at pump startup. The alarm can be reset, or the flow time

delay temporarily increased to allow for pipe filling.