Installation

AAON equipment has been designed for
quick and easy installation.

Unit Location
The curb should be mounted first and must
be located so that duct connections will be
clear of structural members of the building.

Verify rooftop or foundation can support the
total unit weight, including accessory
weights.

























Do not position flue opening to discharge
into a fresh air intake of any other piece of
equipment. Unit should also be installed so
that the flow of combustion intake air is not
obstructed from reaching the furnace.

Vent opening must not be blocked by snow.
A minimum 12” curb must be used or the

vent outlet shall be greater than 12” off the
ground or roof.

Flue gas is dangerously hot and contains
containments. The user is responsible for
determining if vent gases may degrade
building materials.

The National Gas and Propane Installation
Code, B149.1 specifies a 6 ft. horizontal
vent terminal clearance to gas and electric
meters and relief devices.

Local codes may supersede or further place
restrictions on vent termination locations.

Table 3 - Unit Clearances

Location

Unit Size

2-6 tons

Front -

(Heat Exchanger)

36”

Back - (Outside Air)

36”

Left Side

24”

Right Side

48”

Top

Unobstructed



Figure 2 - RQ Series Orientation


Setting the Curb

Make openings in roof decking large enough
to allow for duct penetration and workspace


When locating gas fired units, it is
recommended the unit be installed so
that the flue discharge vents are
located at least 120 inches away
from any opening through which
combustion products could enter the
building.

WARNING

Back

Right Side

Front


Distances

from

adjacent

public

walkways,

adjacent

buildings,

operable

windows

and

building

openings, shall conform to local
codes and/or the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the
National Gas & Propane Code, CSA
B149.1

WARNING