Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.

If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.

Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.

Table 4 - Control Wiring

Wire Size (Stranded)

- Copper Conductors

Only

Total Wire Distance

Allowable

20 AWG

200 ft

18 AWG

350 ft

16 AWG

500 ft

14 AWG

750 ft

12 AWG

1250 ft


Take the total wire distance allowable and
divide by the number of wires to be
connected. This indicates the distance
allowable for that size wire. The wiring to
the unit must not exceed the total wire
distance allowable. If the voltage at the
connectors is less than 21 VAC, isolation
relays must be installed. If under external
control 21 VAC must be field verified.

All external devices must be powered via a
separate external power supply.

Example:
A total of 8 wires must be pulled 75ft to
control the unit. What size wire should be
used?

According to the Table 3, 16 AWG allows
for 63ft (500 ft/8 wires) and 14 AWG allows
for 94ft (750 ft/8 wires). Thus, 14 AWG
should be used.

Gas Heating















Verify the unit nameplate agrees with the
proper gas supply type and amount.

Gas piping must be installed in accordance
with local codes, or in the absence of local
codes, installation must conform to the
current (United States) National Fuel Gas
Code ANSI-Z223.1/NFPA 54 or the current
(Canada)

National

Fuel

&

Propane

Installation Code CSA B149.1 or B149.2.

Table 5 - 2-6 ton Gas Connections

Model

Option

B2

Input

MBH

Connections

Quantity

Size

1

60.0

1

1/2”

3

100.0

5

140.0

7

160.0


FOR YOUR SAFETY

Read

the

entire

gas

heating

installation section of this manual
before beginning installation of the
gas heating section.

If you do not follow these instructions
exactly, a fire or explosion may result
causing property damage, personal
injury, or loss of life.

WARNING