Condenser fan ec motor startup, Table 16 - ec condenser fan cycling options – AAON RQ-006 User Manual

Page 59

Advertising
background image

59

If there is no rotation and/or no speed
change, try the following:

1. Check the line-to-line voltage on the

fuse block connected to the supply fan
motor and ensure it is between 187VAC
to 264VAC

2. Turn the potentiometer to 50%
3. Energize the BC relay by making a

blower call.

4. Check DC voltage on S1 (-) and S2 (+),

0-10VDC signal on S1 & S2 sets the
speed of the motor – thus 0VDC is no
speed and 10VDC is full speed.

5. If DC Voltage is present on S1 & S2

then ensure that BC (blower relay) is
energized and is passing the DC voltage
through to the motor. If BC is not
energized then check wiring for 24VAC
blower call.

6. If no DC voltage is present on S1 & S2

then check S1 (-) & S3 (+), this is the
+10VDC output from the motor that is
supplied to the Potentiometer for speed
control.


If the following troubleshooting suggestions
do not solve the issue, contact AAON for
assistance.

Condenser Fan EC Motor Startup
The fan cycling option uses a fan cycle
switch to switch between one of the discrete
speed inputs (see Table 16) on the motor
thus cycling between two preset speeds
based upon discharge pressure of the unit.
By connecting 24VAC to a single or
combination of the yellow, white, or orange
wires, the motor will run at the discrete
speeds in Table 12.

WattMaster

Condenser

Head

Pressure

Module is used for variable speed control of
the motor to maintain a head pressure. The
motor should be factory wired to the PWM
outputs of the WattMaster Condenser Head
Pressure Module. See WattMaster literature
for

further

information

(http://www.orioncontrols.com).

Note
High voltage wires out of the motor:
Black & Brown – 1 Phase Line Voltage
Green - Ground

Low control voltage wires out of the motor:
Blue – Common
Yellow

Variable

Speed

Control

Table 16 - EC Condenser Fan Cycling Options

Color

Terminal

Customer
Connection

Option 1

Option 2

Option 3

Option 4

Option 5

Black

0.50 BWS

L1

208-230 VAC

208-230 VAC

208-230 VAC

208-230 VAC

208-230 VAC

Brown

0.50 BWS

L2

208-230 VAC

208-230 VAC

208-230 VAC

208-230 VAC

208-230 VAC

Green

#10

EYELET

Ground

GND

GND

GND

GND

GND

Blue

0.50 BWS

Common

Common

24 VAC

24 VAC

24 VAC

24 VAC

Yellow

0.50 BWS

Signal

PWM

24 VAC

24 VAC

White

0.50 BWS

Signal

24 VAC

24 VAC

Orange

0.50 BWS

Signal

24 VAC

24 VAC

RPM

300-1100

300

500

850

1100

Rotation

CCW

CCW

CCW

CCW

CCW

ECM Toolbox ID

Variable

Speed 4

Speed 3

Speed 2

Speed 1

20% PWM RPM

300

100% PWM RPM

1100