General Information


RN Series packaged rooftop units, heat
pumps and outdoor air handling units have
been designed for outdoor installation only.
Units are assembled, wired, charged and run
tested at the factory.

Startup and service must be performed by a
Factory Trained Service Technician.

























Certification of Gas Heat Models
a. AAON gas heat exchangers have

successfully completed 10,000 burner
operation cycles and corrosion resistance
as specified per test standard ANSI
21.47. All gas heat exchangers used in
AAON appliances are certified for use
downstream of evaporator or cooling
coils.

b. Certified as a Category III forced air

furnace with or without cooling.

c. Certified for outdoor installation only.
d. Certified

for

installation

on

a

combustible roof with a minimum of 12”
high curb.

Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air heating system

with or without cooling.

b. Certified for outdoor installation only.
c. Certified

for

installation

on

a

combustible roof with a minimum of 12”
high curb.


Certification of Electric Heat Models
a. Certified as an electric warm air furnace

with or without cooling.

b. Certified for outdoor installation only.
c. Certified

for

installation

on

a

combustible roof with a minimum of 12”
high curb.


Certification of Cooling Models
a. Certified as a commercial central air

conditioner with or without electrically
operated compressors.

b. Certified for outdoor installation only.
c. Certified

for

installation

on

a

combustible roof with a minimum of 12”
high curb.

d. Certified with refrigerant R-410A coils

or with chilled water cooling coils.


Codes and Ordinances
RN Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236,
ANSI Safety Standard Z21.47b-2008/CSA
2.3b-2008, and ANSI Safety Standard
Z83.8-2006/CSA 2.6-2006.

System should be sized in accordance with
the

American

Society

of

Heating,

Refrigeration

and

Air

Conditioning

Engineers Handbook.


Improper

installation,

adjustment,

alteration, service, or maintenance
can

cause

property

damage,

personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.

WARNING


These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.

CAUTION