Adjusting sub-cooling and superheat temperatures, Table 25 - acceptable refrigeration, Caution – AAON RN-140 User Manual

Page 77

Advertising
background image

77

Table 25 - Acceptable Refrigeration

Circuit Values

Air-Cooled Cond./Air-Air Heat Pump

Sub-Cooling

12-18°F

Sub-Cooling with

Hot Gas Reheat

15-22°F

Superheat

8-15°F

Water-Cooled Cond./Water Source Heat

Pump

Sub-Cooling

4-8°F

Superheat

8-15°F












Adjusting Sub-cooling and Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator

superheat

is

within

the

temperature range as shown in the table
above (high superheat results in increased
sub-cooling).

Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.









The system is undercharged if the superheat
is too high and the sub-cooling is too low

Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.

If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.


DO NOT OVERCHARGE!


Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.

CAUTION


Thermal expansion valve must be
adjusted to approximately 8-15°F of
suction superheat. Failure to have
sufficient superheat will damage the
compressor and void the warranty.

CAUTION