Table 13 - 55, 65 and 75-140 ton gas connections, Table 14 - natural gas (ft, Hr) maximum piping capacities – AAON RN-140 User Manual

Page 53: Figure 30 - rn series gas heat exchanger

Advertising
background image

53

Table 13 - 55, 65 and 75-140 ton Gas

Connections

Model

Option

B2

Input

MBH

Connections

Quantity

Size

M

800

2

1” NPT

N

1600

2

1-1/2”

NPT

P

2400


After verifying gas inlet pressure and
manifold pressure the service technician
must time the gas flow rate through the gas
meter with a stopwatch to verify the gas
input rate.

Unit nameplate input rate value has been
calculated at the altitude where the unit was
shipped. Above 2,000 ft the input rate is
adjusted 4% for every 1,000 ft.

Figure 30 - RN Series Gas Heat Exchanger









Table 14 - Natural Gas (ft

3

/hr) Maximum Piping Capacities

Specific Gravity = 0.6, Supply Pressure ≤ 0.5 psi, Pressure Drop = 0.5” w.c.

Pipe Size

Length of Pipe

20 ft

50 ft.

100 ft.

150 ft.

200 ft.

1/2”

120

73

50

40

35

3/4”

250

151

103

84

72

1”

465

285

195

160

135

1-1/4”

950

580

400

325

280

1-1/2”

1460

900

620

500

430

2”

2750

1680

1150

950

800

2-1/2”

4350

2650

1850

1500

1280

Table 15 - Propane (kBtu/hr) Maximum Piping Capacities

Specific Gravity = 1.52, Supply Pressure = 11” w.c., Pressure Drop, 0.5” w.c.

Pipe Size

Length of Pipe

20 ft

50 ft.

100 ft.

150 ft.

200 ft.

1/2”

189

114

78

63

55

3/4”

393

237

162

132

112

1”

732

448

307

252

213

1-1/4”

1496

913

630

511

440

1-1/2”

2299

1417

976

787

675

2”

4331

2646

1811

1496

1260