Wiring the rear panel, Preparing/connecting captive wires, Wiring guidelines – AMX AXB-TM5 User Manual

Page 8: Using the axlink connector for data and power

Advertising
background image

Connection and Wiring

4

AXB-TM5 Television Manager

Wiring the Rear Panel

Preparing/connecting captive wires

You will need a wire stripper and flat-blade screwdriver to prepare and connect the captive wires.

1.

Strip 0.25 inch of wire insulation off all wires.

2.

Insert each wire into the appropriate opening on the connector according to the wiring

diagrams and connector types described in this section.

3.

Do not tighten the screws excessively; doing so may strip the threads and damage the

connector.

Wiring Guidelines

The AXB-TM5 requires 12 VDC power to operate properly. The power can be supplied by the

AMX system's AXlink cable or with an optional 12 VDC power supply. The maximum wiring

distance between the control system and AXB-TM5 is determined by power consumption, supplied

voltage, and the wire gauge used for the cable. The following table lists wire sizes and the

maximum lengths allowable between the AXB-TM5 and the control system. The maximum wiring

lengths are based on a minimum of 13.5 volts available at the control system's power supply.

If the AXB-TM5 is installed farther away from the control system than recommended in the above

table, connect an external 12 VDC power supply to the two-pin PWR connector on the rear panel.

Using the AXlink connector for data and power

To use the AXlink 4-pin connector for data communication and for power supply, the incoming

PWR and GND cable from the control system must be connected to the AXlink cable connector

going to the control system as sown in the AXlink wiring diagram (FIG. 3).

Never pre-tin wires for compression-type connections.

Do not connect power to the AXB-TM5 until the wiring is complete. If you are using
power from AXlink, disconnect the wiring from the control system before wiring the
AXB-TM5. If you are using an optional 12 VDC power supply, apply power to the
AXB-TM5 only after installation is complete.

Wiring Guidelines @ 200 mA

Wire size

Maximum wiring length

18 AWG

586.55 feet (178.78 meters)

20 AWG

371.29 feet (113.17 meters)

22 AWG

231.48 feet (70.56 meters)

24 AWG

145.91 feet (44.47 meters)

FIG. 3 AXlink connector wiring diagram

PWR +

AXP/TX

AXM/RX

GND -

PWR +

AXP/TX

AXM/RX

GND -

To the AXB-TM5

To the Control system