Operationandfunction

6.3.3.

running the automatic adjustment for TUNE FUNCTIONS

X.TUNE Automatic adjustment of the positioner
PQ-LIN

5)

Automatic linearization of the process characteristic

P.TUNE

5)

Self-optimization of the process controller

The

TUNE FUNCTIONS must be run for a function check of the positioner / process controller to adjust

to specific local features.

Warning!

while the TUNE FUNCTIONS is running, the valve automatically moves from its current position!
• Never run

TUNE FUNCTIONS while a process is running!

• Take appropriate measures to prevent the system / positioner / process controller from being unintentionally

actuated!

noTe!

avoid maladjustment of the controller due to an incorrect compressed air supply or applied operating
medium pressure!

• Run

TUNE FUNCTIONS whenever the compressed air supply (= pneumatic auxiliary energy) is available

during subsequent operation.

• Run the

TUNE FUNCTIONS function preferably without operating medium pressure to exclude interference

caused by flow forces.

Set up connection

Figure 21:

Starting TUNE FUNCTIONS

5)

only with process controller Type 8693 and 8793