Operationandfunction

6.6.

error messages

6.6.1.

error messages while the X.TUNE function is running

Display

Cause of fault

remedial action

ERR 1:
No pilot air

No pilot air connected

Connect pilot air

ERR 2:
Pilot air failed during
X.TUNE

Pilot air failure while the

X.TUNE function was

running

Check pilot air supply

ERR 3:
Control system
deaeration side leaking

Actuator or control system deaeration side
leaking

Not possible, device defective

ERR 4:
Control system aeration
side leaking

Control system aeration side leaking

Not possible, device defective

Table 5:

Error messages for X.TUNE

6.6.2.

error messages while the PQ.LIN function is running

Display

Cause of fault

remedial action

ERR 1:
No pilot air or no
change to process
variable

No compressed air connected

No change to process variable

Connect compressed air

Check process and, if required,
switch on pump or open the shut-
off valve.

ERR 2:
Current node (valve
stroke) was not reached

Current node of the valve stroke was not
reached, as

• Pilot air failed during

P.Q’LIN

X.TUNE was not run.

Check pilot air

Run

X.TUNE

Check process sensor

Table 6:

Error messages for PQ.LIN