English, 5 parameters – Burkert Type TAT002 User Manual

Page 12

Advertising
background image

10 - 0911

english

2.5

Parameters

Control

Hy1

Hysteresis 1

Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero. The control function is predefined
with S1C.

Hy2

Hysteresis 2

Switch hysteresis of Set-value 2 with
positive or negative values(as Hy1).
The control function is predefined with
S2C.

LS1

Lowest set-value setting

Set-value limits 1 for operator

LS2

Lowest set-value setting

Set-value limits 2 for operator

US1

Highest set-value setting

Set-value limits 1 for operator

US2

Highest set-value setting

Set-value limits 2 for operator

S1C

Control function 1

in = inverted (Heating, humidifying)
dir = direct (cooling, dehumidifying)

S2C

Control function 2

in = inverted (heating, humidifying)
dir = direct (cooling, dehumidifying)

AC

Minimum switch-off period

0 ... 250 sec relay switch-off period

ouc

Dependency of the

diP = dependent

set-values

ind = independent

on

Minimum switch-on period

0...250 sec relay switch-on period

ono

Minimum delay

0...120 min; minimum delay between two
activations of the control relay.

Alarms

ALC

Configuration

rE = relative to the set-value (in Kelvin)

Temperature alarm

Ab = absolute values (in °C)

ALL

Low temperature alarm

If SET - ALL is undershot, a low
temperature alarm will be triggered after
the delay time ALd.

ALU

Over-temperature alarm

If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.

ALd

Alarm delay

0...999 min; Minimum time in which the

at temperature

conditions for an alarm situation

Overshoot/Undershoot

must be present.