2.3

Before the installation

PREDEFINE THE SENSOR TYPE

Hold down the SET +

buttons for 3 seconds.

Select the parameter Pbc (sensor type) and then
confirm with the SET button to see the current
default.

Type TU (temperature controller):

J = Thermoelement J; Pt = Pt100;
C = Thermoelement K; Ptc = PTC;
S = Thermoelement S; ntc = NTC

Type AU
(control devices with voltage/current input):
cur = 4...20 mA; 0-1 = 0...1 V; 10 = 0...10 V

Confirm the default with the SET button.

Briefly switch off the power to the device.

The configurable input type is noted on the controller
label. Please enter this input type if it does not
corresponds to the connected sensor type.

LOCKING AND UNLOCKING THE KEYPAD

Hold down the buttons

and

for at least 3

seconds. The POF message appears on the
display

. The keyboard is locked. The POF

message also appears if you hold down a button for
longer than 3 s.

The keyboard will be unlocked if you hold down
the buttons

and

for 3 s. POn appears in the

display for a few seconds.

CHANGING THE DEFAULT PARAMETERS

Enter a desired value with SET +

or

.

Then confirm with the SET button.

Enter a desired parameter with

or

.

NOTE

All the parameter values can only be seen by repeatedly
pressing the SET1 buttons.