English, 6 controlling the loads – Burkert Type TAT002 User Manual

Page 15

Advertising
background image

0911 - 13

english

HEATING

Parameter S1C = in; The value HY has been preset to 2 K in the factory.

If the temperature falls below the value SET-HY, the controller output will be
switched on and will be switched off again when SET is exceeded.

2.6

Controlling the loads

CONTROLLER OUTPUT

The control is dependent on the measurement temperature (= sensor
temperature). Program the control direction (heating or cooling) with the parameters
S1C and S2C.

S1C = dir

Cooling

Set =

Set-value

S1C = in

Heating

Hy =

Switch hysterisis

COOLING

Parameter S1C = dir; The value HY has been preset to 2K in the factory.

If the temperature exceeds the value SET + HY, the compressor is switched on
and will be switched off again when the temperature falls below SET.

t

temperature

compessor

SET

SET+HY

ON

t

ON

t

t

temperature

SET

SET-HY

heat

Advertising
This manual is related to the following products: