English – Burkert Type TAT002 User Manual

Page 14

Advertising
background image

12 - 0911

english

NOTE

You can access hidden parameters by holding down the
keys SET + for 3 sec in the programming level HY. The
message Pr2 appears.

Digital inputs

HES

Temperature increase/

Set-value is increased/lowered by HES

Reduction

during an energy-saving phase
Activation via digital input
(i1F = Es).

i1F

Function of the digital

EAL = external alarm; OFF = unused;

Input

bAL = serious external alarm;
Es = Energy saving mode Start/Stop;
onF = switch the device ON/OFF
externally;
C-H = reverse the control effect

i1P

Polarity of the digital

CL: active with closed contact

input

OP: active with opened contact

did

Alarm delay time

For i1F = EAL or i1F = bAL.

of the digital input

The corresponding alarm then takes

(0...120 min)

place display or message.

Miscellaneous

Adr

Serial address RS485

Address for XJ500 recording

(1...247)

system. Identifies the device if it
is linked into a ModBUS-compatible
system.

OnF

Set device to STAND-BY

no = not possible via keyboard
yes = STAND-BY can be activated by
holding down the SET button

for

at least 4 sec. If you want to change the
set-value, hold down the SET button for
approx. 2 sec.

Ptb

Number of the parameter-

only read-out value

table

rEL

Version

only read-out value

Pr2

Display of the parameters

display only

in Level Pr2