English – Burkert Type TAT002 User Manual

Page 17

Advertising
background image

0911 - 15

english

4

ASSEMBLY, INSTALLATION AND COMMISSIONING

4.1

General information regarding the installation and operation

ATTENTION!

Do not lay cables for inputs next to lines carrying voltage.

Avoid heavy vibrations, aggressive gases, heavy soiling
and damp.

NOTE

Before connecting the device, check that the power supply
corresponds to the values shown on the rating plate.

Observe the maximum loading of the relay contacts (see
Technical data).

Ensure that you install all sensors with sufficient separation
from lines carrying voltage, in order to avoid incorrect
temperature measurements and to protect the device from
voltage interference over the sensor inputs.

Panel

Mounting bracket

4.2

Assembly

The device is designed for panel mounting in a cutout of 71 x 29 mm, and is
secured with mounting brackets.

In order to ensure the IP65 front protection, a rubber seal must be fitted begind
the front frame (optional with RG-C).

The ambient temperature for trouble-free operetion is in the range from
0 ... +60°C.

Ensure sufficient ventilation through the cooling slots.

Advertising
This manual is related to the following products: