Dimensions

An FMR is delivered completely assembled with wired pressure transmitter lines
(the version shown was assembled without a temperature transmitter).

TopControl Type 8630


actuator, control valve Type
2712


cable from pressure transmitter
to TopControl Type 8630


pressure transmitter Type 8323


flange to DIN EN 1092-1

ATTENTION!

On assembly, be sure to
connect an intake
section to EN ISO 5167-
1 upstream. The
required outlet sections
are already integrated
into the FMR (6 x DN).

DN Pipe connection [mm]

L [mm]

HG mm]

ØE [mm]

15

330

391

101

25

500

389

101

40

700

481

127

50

800

518

157

65

1000

547

157

80

1200

623

261

100

1400

633

261


Intake section to EN ISO 5167-1

Action diagram of the FMR


For process parameters on the FMR, the
volumetric flow through the valve or the flow velocity
of the medium at the defined pipe as reference may
be selected with the operating software (cf. menu
item P.CONTRL\P.CO SCAL).