Burkert Type 8750 User Manual

Page 16

Advertising
background image

I

NSTALLATION

14 - 8750

Program sequence on commissioning

Menu item

Required
settings
(factory settings)

Explanations / Remarks

EEPROM

After ca. 5 sec,
automatic
initialization

Program parameters are loaded from an EEPROM;
then the process operating level is active; the yellow
LED in key

flashes;

POS 0

POS displayed

on the display, an apostrophe (') runs from left to
right; change to configuration level by keeping key

depressed until ACT.FUNC appears on the

display

ACT.FUNC

FUNC SNGL

Program stands in the first main menu item

ACT.FUNC. The operating mode of the actuator
was already set in the factory (single-acting= SNGL;
double-acting = DOUB); change if necessary with
an arrow key; confirm setting with

and return to

ACT.FUNC

INPUT

INP 4'20A

The standard signal set 4'20A (4 to 20 mA) may be

changed with an arrow key
(choose between 4'20A; 0'20A; 0' 10V and 0'5 V);
confirm settings with

and return to INPUT

CUTOFF

CUT

0

CUT

T

100

Tight-closing function of the process controller on
reaching the value in %; lower

and upper

T

values

may be changed with the arrow keys;
confirm setting with

and return to

CUTOFF

X.TIME

T.OPN 60

T.CLS 60

Setting of the floating time between opening and
closing is performed by Autotune; manually, the
arrow keys may be used to set a value from the
range from 1 to 60 s;
confirm setting with

and return to X.TIME

P.CONTRL

Program stands in the main menu item P.CONTRL;
the required process controller parameters are now
set

P.CODBND

DBND 1.0

Specify a dead band for the actuating signal, within

which the the controller does not react; change the
position with

and the values with arrow keys;

confirm setting with

and return to P.CO DBND

P.CO PARA

KP 1.0

TN 999.9

TV 000.0

X0 0

In the factry, the process controller is set to a P-
controller; the final controller parameters are
determined later by Processtune; change the position
with

and the values with the arrow keys; confirm

setting with

and return to P.CO PARA

P.CO SETP

SETP INT

Set setpoint to internal (INT) or external (EXT);

confirm setting with

and return to P.CO SETP

Further to P.CO INP