Burkert Type 8709 User Manual

Page 36

Advertising
background image

36

Operation and function

possible binary input functions
function

description

Actuate Autotune

Start of Autotune function for optimization of the control parameters
to the conditions available in the system, description see Chapter

8.3.

Functions of the LFC / LFM.

Switch to characteristic 2

The calibration curve saved under Gas 2 as well as using all param-
eters entered there.

Reset totalizer

The integrated totalizer (quantity integrator) is reset to 0.

Start set-point value profile

Start of the saved set-point value profile, description see Chapter

8.3.

Functions of the LFC / LFM.

Control mode

Switch to control mode for the systematic opening of the integrated
proportional valve, description see Chapter

8.3. Functions of the LFC /

LFM.

Correct safety value

5)

Correct the safety value stored in the device as a flow-rate set-point
value.
The flow-rate set-point value applied analogically or transmitted by the
field bus is ignored in this case.

Close valve completely

5)

Valve closed completely.
The flow-rate set-point value is ignored in this case.

Open valve completely

5)

Valve opened completely.
The flow-rate set-point value is ignored in this case.

5)

The operating principle of the binary input (active / inactive) can be selected for these functions

Binary input functions

Table 5:

standard assignment of the binary inputs:
input

configuration

Binary input 1

LFC: Actuate Autotune

LFM: unused

Binary input 2

LFC: Open valve completely

LFM: unused

Binary input 3

6)

unused

6)

not available for 8718 / 8708

Standard assignment of the binary inputs

Table 6:

english

Type 8718, 8719 / 8708, 8709