Burkert Type 8709 User Manual

Page 37

Advertising
background image

37

Operation and function

Binary outputs

The LFC / LFM feature binary outputs to indicate operating states, and limit values which exceed maximum/drop
below minimum or faults.

possible binary output functions
function

description

unused

No function is assigned to the binary output.

Power on

The power supply is on.

Autotune active

The Autotune function is active.

Gas 1 or 2 active

The calibration curve 1 or 2 is currently selected.

User-defined calibration active

The device operates at the calibration adjusted by customer.

Binary input 1, 2 or 3 active

Binary input 1, 2 or 3 is set.

Activate binary output by field bus

The status of the binary outputs is specified via the field bus or the
serial interface.

Correct safety value active

The set safety value has been corrected.

Set-point value profile active

The set-point value profile stored in the device has been corrected.

Control mode active

The control mode is active, i.e. the specified set-point value is outputed
directly as an actuating variable of the proportional valve.

Close valve completely active

The close valve completely function is activated.

Open valve completely active

The open valve completely function is activated.

Defective power requirement

The power requirement of the device is monitored.
If this value is outside defined limits, this function is actuated. A
too high or too low power requirement, may for example, indicate a
defective device.

Defective internal power supply

The operating voltage of the device is monitored.
If the defined limits exceed the maximum or drop below the minimum,
this function is actuated.

Defective power supply of the sensor

The power supply voltage of the sensor is monitored.
If the defined limits exceed the maximum or drop below the minimum,
this function is actuated.

Defective data storage

If data storage is in the non-volatile memory of the device, a fault has
occurred.

Sensor fault

The device is able to detect a defective sensor via a self-test.
If this is the case, this function is activated.

MFI fault

The field bus module (MFI) is defective or incorrectly equipped.
Field bus communication is not possible.

x limit

The actual value has exceeded or dropped below a freely adjustable
limit value.

w limit

The set-point value has exceeded or dropped below a freely adjustable
limit value.

y2 limit

The actuating variable has exceeded or dropped below a freely
adjustable limit value.

Totalizer limit

The totalizer has exceeded or dropped below a freely adjustable limit
value.

Binary output functions

Table 7:

english

Type 8718, 8719 / 8708, 8709