Functions

10.1.2. CUTOFF -

sealing function for the position controller

This function causes the valve to be sealed outside the control range.

Controlled operation is resumed with a hysteresis of 1 %.

Factory settings: DIP switch 2 set to OFF (no sealing function)

DiP switches Position

Function

2

ON

Sealing function active. The valve completely closes below 2 %

8)

and opens above 98 % of the set-point value (

CUTOFF)

OFF

No sealing function

Table 17:

DIP-switch 2

The communications software can be used to change the limits for the position set-point value as a percentage.

The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the sealing function (

CUTOFF) which are changed via the communications

software are not active unless DIP switch 2 in the positioner is set to ON.

Valve stroke
[%]

Adjustable from 75 – 100 %

Set-point value [%]

Adjustable from 0 – 25 %

Figure 13:

CUTOFF graph

8)

Factory settings can be changed via communications software.