Functions

10.1.3. CHARACT -

Transfer characteristic between input signal
(position set-point value) and stroke

Characteristic (customer-specific characteristic)

This function can be used to activate a transfer characteristic with respect to set-point value (set-point position)
and valve stroke for correction of the flow or operating characteristic.

The transfer characteristic can be changed via the communications software only.

Factory settings: DIP switch 3 set to OFF (linear)

DiP switches Position

Function

3

ON

Correction characteristic for adjustment of the operating character-
istic (linearization of the process characteristic

CHARACT)

9)

OFF

Linear characteristic

Table 18:

DIP switch 3

The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the correction characteristic (

CHARACT) which are changed via the communica-

tions software are not active unless DIP switch 3 in the positioner is set to ON.

Characteristics which can be selected via the communications software:

Characteristic

Description

Linear

Linear characteristic

1 : 25

Equal percentage characteristic 1 : 25

1 : 33

Equal percentage characteristic 1 : 33

1 : 50

Equal percentage characteristic 1 : 50

25 : 1

Inversely equal percentage characteristic 25 : 1

33 : 1

Inversely equal percentage characteristic 33 : 1

55 : 1

Inversely equal percentage characteristic 55 : 1

FREE

User-defined characteristic, freely programmable via nodes

Table 19:

Selection of characteristics

A detailed description of the characteristics can be found in the operating manual for the communications
software for positioners.

9)

The characteristic type can be changed via the communications software only.

english

Type 8791

Advertising