Outputs wiring, Output on/off 1250 hz, Output 0-4÷20ma – Burkert Type 8055 User Manual

Page 15

Advertising
background image



SE 56

15

210_EN_BU_4_3_5X.d

oc

16 (out1)
18 (out2)

17 (out1)
19 (out2)

43V

30

29

43V

24V COMMON

+24V INTERNAL

0/4..20mA OUT

mA

9 (+)

10 (-)

I




























Output on/off 1250 Hz

Opto-insulated output with collector and
emitter terminals floating and freely

connectable
Maximum switching voltage: 40 Vdc

Maximum switching current: 100mA
Maximum saturation voltage between

collector and emitter @100mA: 1,2V
Maximum switching frequency (load on

the collector or emitter, RL=470

,

VOUT=24Vdc): 1250Hz

Maximum reverse current bearable on the

q Opto-insulated output
q Maximum load 1000 ohm
q Maximum voltage without load 27 Vdc
q Refresh frequency equal to the sample frequency

of the connected sensor

q protected against persistent over voltages till 30

Vdc

q Opto-insualted output with collector and emitter terminals

floating and freely connectable. In order to get the maximum

speed performances it is necessary to connect the emitter to
the common terminal of the outputs (0V), while the load has

to be on the collector. This output is internally connected to

the power supply source 24 Vdc available on the terminal
block.

q Maximum switching voltage: 40Vdc
q Maximum switching current: 100mA
q Maximum saturation voltage between collector and emitter

100mA, load on the collector and internal power supply: 0,3V

q Maximum saturation voltage between collector and emitter

100mA, load on the emitter and internal power supply: 3V

q Maximum switching frequency, load on the collector and

internal power supply: (RL=470

, VOUT=24Vdc): 12500Hz

q Maximum switching frequency, load on the emitter or

external power supply: (RL=470

, VOUT=24Vdc): 2500Hz

q Insulation from the other secondary circuits (except 24V and

4…20mA outputs): 500 Vdc

OUT 1/OUT 2 standard - OUT 3/OUT 4 with modules (page 9)

Only with ME 201 module

Output on/off 12500 Hz

The converter detect a loss of load on the 4÷20mA output; to disable this

function set the value "mA Val. Fault" to 0 ( pag 28 Pos. 4.7)

OUTPUTS WIRING

Output 0-4÷20mA