Table 3: Diagram flow/ fluid velocity/ DN of S020 fitting (on left) and S030 fitting-sensor (on right)

Example: for a nominal flow = 10 m

3

/h and an optimal flow velocity between 2 and 3 m/s.

use a DN40 fitting (or DN50 for the asterisked fittings).

0.1

0.3 0.5 1

3 5 10

0.01

0.02

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

m

3

/h

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

2000

3000

l/min

0.3 0.5 1

3 5 10

30

m/s

fps

US gpm

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

DN 65

DN 50 (DN65)*

DN 40 (DN50)*
DN 32 (DN40)*
DN 25 (DN32)*

DN 20 (DN25)*

500

1000

2000

2000

5000

10000

5000

20000

5000

10000

20000

30000

50000

100000

DN 400

DN 350

DN 300

DN 250

DN 200

DN 150

DN 125
DN 100

DN 80

Flow rate

Fluid velocity

Example

1)

l/min

DN 65

DN 50 (DN65)*

DN 40 (DN50)*

DN 32 (DN40)*

DN 25 (DN32)*
DN 20 (DN25)*
DN 15 (DN15 / DN20)*

5000

1000

100

3

2
1

20
10

0.5

5

0.3

0.2

500

50

0.01

0.02

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

500

m3/h

m/s

DN 08
DN 06

fps

gpm

2000
1000

500

200

20
10

0.5

0.2

0.1

0.05

100

50

0.1 0.2 0.3 0.5

1

2 3

5

10

0.3 0.5

1

2 3

5

10

20 30

5

2
1

200

2000

Flow rate

Fluid velocity

* For the fittings:
• with external thread connections acc. to SMS 1145,
• with welding end connections acc. to SMS 3008, BS 4825 / ASME BPE or DIN 11850 Rg 2,
• Clamp acc. to SMS 3017 / ISO 2852, BS 4825 / ASME BPE or DIN 32676.

1)

The device cannot be installed on the DN20 fittings listed above

13

Installation