Burkert Type 8035 User Manual

Page 30

Advertising
background image

28

Installationandwiring

Type 8025 /8035 Batch

terminal block 1
PE:▶factory▶wired▶shield.
terminal block 2
•▶ NC:▶not▶connected
•▶ L+:▶V+▶(red▶wire,▶factory▶wired)
•▶ L-:▶0V▶(black▶wire,▶factory▶wired)
•▶ PE:▶protective▶earth,▶factory▶wired
•▶ P-:▶negative▶transistor▶output▶(DO1)▶(brown▶wire,▶factory▶wired)
•▶ P+:▶positive▶transistor▶output▶(DO1)▶(white▶wire,▶factory▶wired)
terminal block 3 "binAry"
•▶ DI1▶to▶DI4:▶4▶digital▶inputs
•▶ DO4:▶transistor▶output
•▶ ISOG:▶ISOGND,▶ground▶common▶to▶the▶4▶digital▶inputs▶and▶the▶

transistor▶output▶DO4.

•▶ PE:▶cable▶shielding
terminal block 4 "flow sensor": Wiring▶the▶remote▶flow▶sensor.▶
The▶wiring▶depends▶on▶the▶type▶of▶output▶signal▶originating▶from▶the▶
flow▶sensor:▶see▶chap.▶„7.6.7“.

terminal block 5:▶wiring▶the▶DO2▶relay▶output.
terminal block 6:▶wiring▶the▶DO3▶relay▶output.▶
terminal block 7
•▶ Terminal▶5:▶not▶connected
•▶ Terminal▶6:▶positive▶27▶V▶DC▶power▶supply,▶available▶to▶energize▶an▶

external▶instrument

•▶ Terminal▶7:▶0V▶(earth▶of▶the▶power▶supply▶available▶to▶energize▶an▶

external▶instrument)

•▶ Terminal▶8:▶protective▶earth▶for▶the▶cable▶shieldings
•▶ Terminal▶9:▶negative▶transistor▶output▶(DO1)
•▶ Terminal▶10:▶positive▶transistor▶output▶(DO1)
terminal block 8:▶wiring▶of▶the▶115/230▶V▶AC▶power▶supply▶

mark

9

:▶time-delay▶fuse▶to▶protect▶the▶115/230▶V▶AC▶power▶

supply

selector

A

:▶see▶chap.▶„7.6.7“.

selector

B

:▶see▶„Fig.▶29“▶page▶33.

selector

C

:▶see▶chap.▶„7.6.7“.

selector

D

:▶see▶chap.▶„7.6.7“.

Fig. 20: Terminal assignment of a wall-mounted version, 115/230 V AC

English

Advertising
This manual is related to the following products: