Burkert Type 8045 User Manual

Page 19

Advertising
background image

19

Installation and wiring

Type 8045

terminal block 1
Iout: 4-20 mA output (AO1)
L+: V+ (positive voltage)
L-: 0V (power supply ground)
PE: functional earth, wired in the factory (see Fig. 15)
P+: positive transistor output (DO1)
P-: negative transistor output (DO1)

terminal block 2
PE: shieldings of both the power supply cable and the AO1
and DO1 output cables

terminal block 3
PE: functional earth of the DI1 digital input
-: negative signal of the DI1 input
+: positive signal of the DI1 input

terminal block 4: wiring the DO2 relay output
terminal block 5: wiring the DO3 relay output

Fig. 12: Terminal assignment

Use switch A to configure the wiring of the 4-20 mA cur-
rent output in sinking or sourcing mode.

Wire the current output

in sourcing mode.

Wire the current output in
sinking mode.

A

SOURCE

SINK

CURRENT

SOURCE

SINK

CURRENT

Fig. 13: Sink/source switch

Use the switch B to lock/unlock the

ENTER

key to prevent

unauthorized access to the configuration of the device.

The

ENTER

key is unlocked (de-

fault position).

The

ENTER

key is

locked.

OFF ON

B

OFF ON

Fig. 14: Switch to lock/unlock the ENTER key

English

Advertising