Wiring the do2 and do3 relay outputs, Wiring the ao1 current output, English – Burkert Type 8045 User Manual

Page 20

Advertising
background image

20

Installation and wiring

Type 8045

Earth cable coming from the housing.

On a version with stainless steel flow sensor, a second cable

is coming from the sensor.

1 2 3 4 5 6

Fig. 15: Connection of the earth wire coming from the housing

(made in the factory)

7.5.3. Wiring the Do2 and Do3 relay

outputs

DO2

DO3

230 VAC

m

3 A

3 A

230 VAC

Fig. 16: Wiring of the DO2 and DO3 relay outputs

7.5.4. Wiring the Ao1 current output

For safety reasons, secure the cables using a non-con-
ducting cable clamp.

The 4-20 mA output can be wired in either sourcing or sinking
mode.

Power supply

4-20mA input at external

device

Position the

A

switch to the right.

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

AO1

A

18-36 V DC

+

-

300 mA

I

+

-

(*)

Fig. 17: Wiring of the 4-20 mA output (AO1) in sourcing mode
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth

English

Advertising