21

Installation and wiring

Type 8045

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

AO1

A

18-36 V DC

+

-

300 mA

I

+

-

(*)

Power supply

4-20mA input at external

device

Position the

A

switch to the left.

Fig. 18: Wiring of the 4-20 mA output (AO1) in sinking mode
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth

7.5.5. Wiring the Do1 transistor output

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

PE

AO1

300 mA

+

-

18-36 V DC

(*)

+

-

+

- 5-36 VDC

PLC

Power supply

Fig. 19: NPN wiring of the DO1 transistor output
*) If a direct earth connection is not possible, fit a 100 nF/50 V
capacitor between the negative power supply terminal and the earth