TIB Hardware Reference

Comparator Wiring Lists

CTI Products, Inc.

68-10911-100

13

7.

Special Installation Instructions

7.1

Unit Address Setting

A TIB must be programmed with two unit addresses:

1. the address of the CIB it will operate with
2. the TIB’s own address

You only need to perform this programming once, at installation time. These
addresses are stored in non-volatile memory so the only reason that you would
have to repeat this step is if you changed the unit address of the CIB or if you
replaced the TIB module.

Before programming the address information into the TIB, determine the unit
addresses of all the MCN modules in the system, following the guidelines in the
Address Planning section of the Monitoring and Control Network System
Manual (reference 1).

Valid ranges for the Group and Module switches are:

• Group number = 00 through FE

• Module number = 0 through F

The steps for programming the unit address of the CIB are:

Step

Action

1

Determine the unit addresses of all the MCN modules in the system.

2

Apply power to the TIB.

3

Place OPTION switch 4 in the UP position.

4

Set the Group and Module switches to the unit address of the CIB
(from step 1) that this TIB will operate with.

5

Press the RESET button on the TIB.

6

The ERR LED will turn on and remain on.

7

Place OPTION switch 4 in the DOWN position.

8

Set the Group and Module switches to the unit address of this TIB
(its own address from step 1).

9

Press the RESET button on the TIB.

10

The ERR LED will turn on momentarily and then turn off.