TIB Hardware Reference

Comparator Wiring Lists

CTI Products, Inc.

68-10911-100

14

For example, Figure 7 shows a system with a single TIB and CIB. The following
steps show how the system might be setup, using the following address
assignments:

• CIB address is Group 00, Module 0

• TIB address is Group 01, Module 0

• HIB address is Group 80, Module 0 (this is set using the MCNCFG

program running on the Local PC)

Step

Action

1

Connect the module’s NETWORK IN and OUT ports as shown in
the diagram.

2

Power on the modules.

3

On the CIB, set the Group switch to 00 and the Module switch to 0.

4

Reset the CIB.

5

On the TIB, place OPTION switch 4 in the UP position.

6

On the TIB, set the Group switch to 00 and the Module switch to 0.
This is the address of the CIB it will work with.

7

On the TIB, set the transmitter bank selector switches to bank 0.

7

Press the RESET button on the TIB.

8

The TIB’s ERR LED will turn on and remain on.

9

On the TIB, place OPTION switch 4 in the DOWN position.

10

On the TIB, set the Group switch to 01 and the Module switch to 0.
This is the TIB’s own address.

11

Press the RESET button on the TIB.

12

The ERR LED will turn on momentarily and then turn off.

COM 2

COM 1

CA-80119-100

CIB

1

COMPARATOR

HIB

P/S

OUT

IN

T

IN

OUT

IN

OUT

T

TSAM

TIB

VOTE LINES

FORCE SELECT

TX SELECT

LOCAL PC

Figure 7 - Unit Address Programming Example