THREE PHASE POWER CONNECTIONS








REQUIREMENTS

Actual 120/208VAC three phase power must be
supplied to operate the AR-1202 in the 3 phase
configuration. This means that the voltage across any
two lines must be 208 VAC. The feed circuit must be
able to supply 80 Amps for each hot line.


THE AR-1202 WILL NOT OPERATE IN A THREE
PHASE CONFIGURATION FROM 2 LINES OF
EITHER A SINGLE OR 3 PHASE SUPPLY
CIRCUIT.



CONNECTIONS

Connect the 3 in hot feed lines to the 3 terminals on
the input power terminal block (H1, H2, H3).

Connect the feed neutral to the NEUTRAL bus bar.

Connect the feed ground t

o the GROUND lug.

HIGH VOLTAGE CIRCUITRY IS EXPOSED
WHEN THE CABINET DOOR IS OPEN. DO NOT
ALLOW THE UNIT TO OPERATE OR HAVE
POWER APPLIED TO IT WHILE THE DOOR IS
OPEN.

See the section SYSTEM POWER SETUP for
operation using 3 phase connections.































POWER IN

3 PHASE

120/208VAC

BLACK

RED

BLUE

BLUE

RED

MARKER

BLACK

MARKER

H1

H3

H2

WARNING

MAKE CERTAIN POWER IS REMOVED

FROM THE FEED CIRCUITS

BEFORE YOU BEGIN INSTALLATION.

THREE PHASE POWER CONNECTIONS