Ar – 1202, Architectural dimmer, Single phase power connections – Lightronics AR1202 User Manual

Page 5

Advertising
background image

Page

5

of

22

AR – 1202

RTC

ARCHITECTURAL DIMMER

Revision

1.93

OWNERS

MANUAL 06/03/2008

www.lightronics.com

Lightronics Inc.

509 Central Drive Virginia Beach, VA 23454

Tel 757 486 3588


SINGLE PHASE POWER CONNECTIONS








REQUIREMENTS

The RA-122 can operate as a single phase unit using
using only 2 phases of a 3 phase power source. This
is NOT RECOMMENDED since it causes an
unbalanced load at the power source.

The feed circuit must be able to supply 120 Amps for
each line.







CONNECTIONS

There are three terminals on the input power terminal
block (

H1, H2, H3

). When operating the AR-1202 on

single phase power, the center (

H2

) terminal is not

used.

The wires connected to the left side of the H2 terminal
contain color coded sleeves (RED and BLUE). These
wires must be moved and distributed to the H1 and H3
terminals. Remove the wires from the H2 terminal
and connect them to H1 and H3 such that the sleeve
color matches the wire colors on H1 and H3.

Connect the feed neutral to the NEUTRAL bus bar.

Connect the feed ground t

o the GROUND lug.


HIGH VOLTAGE CIRCUITRY IS EXPOSED WHEN
THE CABINET DOOR IS OPEN. DO NOT ALLOW
THE UNIT TO OPERATE OR HAVE POWER
APPLIED TO IT WHILE THE DOOR IS OPEN.



























WARNING

MAKE CERTAIN POWER IS REMOVED

FROM THE FEED CIRCUITS

BEFORE YOU BEGIN INSTALLATION.

POWER IN

SINGLE PHASE

120/240 VAC

BLACK

RED

BLUE

BLUE

RED

MARKER

BLACK

MARKER

H1

H3

H2

NOT

USED

SINGLE PHASE POWER CONNECTIONS