SPECIFICATIONS

XBDM MODEL

XBDM-1015LV XBDM-1020LV XBDM-1030LV XBDM-1020HV*

POWER RATING

15A / 120VAC 20A / 120VAC 30 A / 120VAC

20A / 230VAC

UTILITY INPUT

5-15P 12FT

5-20P 12FT

L5-30P 6FT

IEC C20

AC FREQUENCY

50 / 60 HZ

MAXIMUM OUTPUT

12A

16A

24A

16A

RECEPTACLES

FRONT OUTPUT

(6) 5-15R

(6) 5-20R

(5) 5-20R

(2) IEC C19 + (4)

IEC C13

REAR OUTPUT

(4) 5-15R

(4) 5-20R

(5) 5-20R

(4) IEC C13

REAR UPS INPUT

(1) 5-15R

(1) 5-20R

(1)L 5-30R

(1)IEC C19

UPS OUTPUT

5-15P 3FT

5-20P 3FT

L5-30P 3FT

IEC C20

TRANSFER SWITCH BREAK
BEFORE MAKE TWO-POLE
(MAX 8ms TRANSFER TIME)

(1) 15A

(1) 20A

(2) 20A

(1) 20A

AC SURGE

MAX SPIKE CURRENT

6500A

ENERGY DISSIPATION

114 Joules

220 Joules

MAX CLAMPING VOLTAGE

330V

775V

INDICATORS

UPS AVAILABLE

RED LED

UTILITY AVAILABLE

ORANGE LED

SURGE PROTECTION

GREEN LED

PHYSICAL

SIZE (1U)

(W x D x H) 17” x 3.5” x 1.75”

WEIGHT

3.5 LBS

*Note: XBDM-1020HV has two different part #’s. Please see Shipping List on next page.