Table 5-3. optomux digital i/o control bytes – Micromod Micro-DCI: 53MC5000 PLC AND PRINTER INTERFACES User Manual

Page 56

Advertising
background image

Table 5-3. OPTOMUX Digital I/O Control Bytes

Title

DDI-A

DDI-B

Set By

Default

Communication Mode - A minimum of one word (16 L-
values) is transferred even if only one L-value is used as
an active indicator of a process event.

0 = No data exchange
1 = Reads only - (PCS

⇐ board).

2 = Reads and writes - (PCS

⇔ board)

3 = Writes only - (PCS

⇒ board)

B664

B640

User

0

Number of Contiguous Active Boards 00-15

B665

B641

User

0

Number of Contiguous Active Boards 16-31

B666

B642

User

0

Number of Contiguous Output Modules for Even Board
Addresses 00-15

B667

B643

User

0

Number of Contiguous Output Modules for Odd Board
Addresses 00-15

B668

B644

User

0

Number of Contiguous Output Modules for Even Board
Addresses 16-31

B669

B645

User

0

Number of Contiguous Output Modules for Odd Board
Addresses 16-31

B670

B646

User

0

Watchdog Delay on Outputs (PCS

⇒ board) of Each Board

Address 00-15:

0 - Watchdog disabled
1 - After 10 seconds, turn-off all outputs.
2 - After 1 minute turn-off all outputs.
3 - After 10 minutes turn-off all outputs.
4 - Watchdog timer disabled.
5 - After 10 seconds turn-on output 0, turn-off all other

outputs.

6 - After 1 minute turn-on output 0, turn-off all other

outputs.

7 - After 10 minutes turn-on output 0, turn-off all other

outputs.

B671

B647

User

0

Watchdog Delay on Outputs (PCS

⇒ board) of Each Board

Address 16-31 - the description is the same as
Addresses 00 - 15.

B672

B648

User

0

53MC9015 53MC5000 PLC and Printer Interfaces

5-10

OPTO