Table 8-3. Koyo PLC Read Control Bytes

Title

Definition

DDI-A DDI-B

Set

By

De-

fault

PLC Address

It is the address of the PLC to be accessed. B664

B640

User

0

Starting PLC Memory
Address (Low)

The two byte PLC memory starting address.
Each byte is a decimal number; however,
both bytes together function as a 16 bit
unsigned binary integer, e.g., the PLC
hexadecimal address 4180

16

would be

entered as 65

10

in the high byte B666 [or

B642] and 128

10

in the low byte B665 [or

B641]. (See Appendix A for decimal
conversions.)

B665

B641

User

0

Starting PLC Memory
Address (High)

B666

B642

User

0

Number of L-Words
to Read

The number of L-words that are to be
accessed from the PLC.

B667

B643

User

0

Number of C-Words
to Read

The number of C-words that are to be
accessed from the PLC.

B668

B644

User

0

Memory Type

This byte must be a 31.

B669

B645

User

0

Communications
Error Code*

0 = no errors. 255 = timeout error - a
timeout error indicates no response came
back from the PLC. 254 = bad checksum
(CRC) - a bad checksum indicates even
though the frame was formatted properly,
the data can not be used. 253 = bad
message - bad message indicates that
errors were found in the predictable portion
of the message from the PLC. 252 and 251
= PCS hardware malfunction.

B672

B648

Soft-
ware

0

Error Count*

This byte is a running total of the non-zero
Communications Error Codes

B673

B649

Soft-
ware

0

*User can reset by writing zeros into the datapoints.

53MC9015 53MC5000 PLC and Printer Interfaces