Table 6-1. PCS Modbus Master Commands

Function

Code

Data

Type

Title

Description

16

L and

C

Preset [Write] Multiple
Registers

This command places specific binary values
into a series of consecutive holding registers.
It can also be used to write L-and C-values
together to the PLC. The L- and C-values are
first written to the PLC holding register memory
segment. The L-values are written in first at
the top of the holding register memory
segment, followed by the C-values. The user
must then move the L-values from the holding
register memory segment to the appropriate L-
value memory segment.

6.4.13 PCS MODBUS MASTER DIAGNOSTIC COMMAND

The Diagnostic command (Function Code 8) provides access to device diagnostic information and
a loopback test that can be used to check the Modbus communications system. The command has
sub-functions called Diagnostic Codes that specify the various types of diagnostic information be-
ing accessed, counters that are being cleared, or the loopback test. The appropriate Modbus docu-
mentation should be referenced to implement the various Diagnostic Codes of the Diagnostic
command. It should also be referenced to determine the significance of the diagnostic information
returned, as it might be register bit defined by PLC type (e.g., bit 9 set in the 484 Controller diag-
nostic register means ROM chip 0000-07FF failed the memory test). The Diagnostic codes are
listed as follows:

Diagnostic Code

Sub-Function

Diagnostic Code

Sub-Function

High

Low

High

Low

00

00

Return Query Data

00

13

Return Bus Exception
Error Count

00

01

Restart Communications
Option

00

14

Return Slave Message
Count

00

02

Return Diagnostic Register

00

15

Return Slave No
Response Count

00

03

Change Input Delimiter
Character

00

16

Return Slave NAK Count

00

04

Force Slave to Listen Only
Mode (LOM)

00

17

Return Slave Busy Count

00

10

Clear Counters and
Diagnostic Register

00

18

Return Bus Character
Overrun Count

00

11

Return Bus Message Count

00

19

Return Overrun Error Count

00

12

Return Bus CRC Error
Count

00

20

Clear Overrun Error Count
and Flag

2 of 2

Section 6. MODBUS RTU Mode

MODBUS2

6-7