53SU6000 INSTALLATION AND SETUP GUIDE

26 Introduction

4.3 INTERFACING WITH THE Micro-PWC GLOBAL DBA

The UdciGDS.ini file (located in the Windows root directory) allows several parameters of the
Micro-PWC Global DBA system to be customized:

[Events]

AREA

This parameter should be set to the area in which all Micro-DCI
events will be reported. This value is ignored if an area as described
in Section 4.0 is assigned.

Values range from 1 to 255.

PRIORITY

This parameter should be set to the priority level at which all Micro-
DCI events will be reported. This value is ignored if a priority as
described in Section 4.0 is assigned.

Values range from 1 to 16.

[Timing]

ATOMSTALESEC

The Micro-PWC system’s Micro-DCI instrument interface provides
values to the various Micro-PWC system displays. This parameter
establishes an upper limit as to how old trend data values may be.
Setting this parameter to low time values produces fresher data but
increases the time required to call up a display for the first time.
Settings are in seconds. Values range from 1 to 65535 seconds.

BKGDDELAYMSEC

This parameter is set by the factory and should not be changed.