PROGRAMMING

ISSUES FOR PROGRAMMING.

- Error light is flashing, PLC is either missing or

damaged.

- Update to newer program
- Installation of new un programmed PLC

MATERIAL REQUIRED.
You will receive two (2) E-proms

- Blank run E-Prom.
- Program Specific E-Prom.

INSTALLATION

1. Turn power off power. (remove existing E-Prom if

present).

2. Insert new “Blank Run” E-Prom.
3. Turn power on for 30 seconds.
4. Turn power off for 10 seconds repeat cycle 3

times.

- Insert program chip (program specific)

Repeat steps 1,3 and 4. Allow light sequence to
complete flashing. Run light should be on STEADY not
flashing
. Error light should NOT be on. Check for proper
input and out put lights on the PLC.
If not, repeat steps 3 and 4 until PLC responds properly.
If the PLC does not accept the program or if questions
contact the “Tech Service Department” at 800-643-9424.

Note: The PLC will maintain the program even if the
power is turned off.

Twido PLC

E-Prom

Prom Location